Getong Energy
+
  • +Power(90-300K)_spec(2475).jpg

+Power(90-300K)

Output power factor 1 N+1 or N+R Parallel Redundancy for power guarantee Modular design decreases MTTR High scalability High reliable operation with redendant power supply in STS Built-in maintenance bypass switch for easy maintenance without interruptible High efficiency double conversion online UPS Adjustable battery numbers User-adjustable charging current Graphic 5.7'' LCD design for easy configuration

Classification:

Customized UPS power supply


Product Description

  Output power factor 1

  N+1 or N+R Parallel Redundancy for power guarantee

  Modular design decreases MTTR

  High scalability

  High reliable operation with redendant power supply in STS

  Built-in maintenance bypass switch for easy maintenance without interruptible

  High efficiency double conversion online UPS

  Adjustable battery numbers

  User-adjustable charging current

  Graphic 5.7'' LCD design for easy configuration

 

MODEL +Power 30U-90HV +Power 42U-120HV +Power 30U-120HV
+Power 30U-80-20KHV
+Power 30U-180HV
+Power 30U-120-20KHV
+Power 42U-200-20KHV +Power 42U-210HV +Power 42U-300HV
PHASE 3-phase in/3-phase out
CABINET CAPACITY* 90KW 120KW 120KW or 80KW 180KW or 120KW 200KW 210KW 300KW
BATTERY TYPE Built-in Battery External Battery
One Power Module Capacity 30KVA/30KW 30KVA/30KW or 20KVA/20W 20KW 30KVA/30KW 30KVA/30KW
Max. Power Module No. 3 4 4 6 10 8 10
Max. Battery Set No.** 3 5 - - - - -
INPUT
Nominal Voltage  3 x 380VAC/400VAC/415VAC (3Ph+N) 
Voltage Range  305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load
Nominal Frequency  50/60Hz (Auto sensing)
Frequency Range  40Hz ~70Hz
Power Factor  > 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi) < 3% @ 100% load
OUTPUT
Nominal Voltage  3 x 380VAC/400VAC/415VAC (3Ph+N) 
Voltage Regulation (Steady state) ≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
Nominal Frequency  50/60Hz
Frequency Range (Synchronized range) 46Hz ~ 54Hz or 56Hz ~ 64Hz 
Overload Capability  1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Harmonic Distortion ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load)
Efficiency  Up to 94.5%
BATTERY / CHARGER
Nominal Voltage  +/-  216V (12V x 36 Pcs)
Maximum Voltage  +/- 240V (12V x 40 Pcs)
Minimum Voltage  +/- 192V (12V x 32 Pcs)
Floating Charge Voltage  2.25V/Cell
Boost Charging Voltage  2.35V/Cell
Temperature Compensation  Yes
Maximum Charging Current (Per Power Module) 8A 8A for 30KW power module
6A for 20KW power module
6A 8A 8A
PHYSICAL
Cabinet Dimension
(D x W x H) mm
1100 x 600 x 1475  1100 x 600 x 2010 1100 x 600 x 1475  1100 x 600 x 1475  1100 x 600 x 2010
Net Weight (kgs) 675 932 335 or 333 437.5 or 434.5 611 549 620
ENVIRONMENT
Operation Temperature  0 ~ 40℃
Relative Humidity  0 ~ 95% non-condensing
Altitude *** <1000m for Nominal power
IP Class  IP 20
MANAGEMENT
RS-232/USB Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 60950-1; IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3

 

  *When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃.

  ** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules.

  ***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.

Model Description Dimension DxWxH(mm) Weight (kg)    
PM-30HV 3P/3P 30KVA/30KW power module 736.5 x 490 x 133 (3U) 34.5    
PM-20HV 3P/3P 20KVA/20KW power module 736.5 x 490 x 133 (3U) 34    
Battery Module 10 pcs of 12V/9Ah batteries  710x107x154 26