Getong Energy
+
  • Giant(10-200K)-spec(2466).jpg

Giant(10-200K)

•Online double-conversion •DSP technology guarantees high reliability •True galvanic isolation transformer design •Control designed to withstand all kinds of loads •Intelligent battery management to prolong battery lifecycle •Independent ventilation enhance durable operation under harsh environment •Adjustable battery numbers •Accept dual-mains input •Parallel operation with up to 4 units (option) •Variety of communication options available •Reverse phase frequency operation and supports non-neutral input

Classification:

Customized UPS power supply


Product Description

  •Online double-conversion

  •DSP technology guarantees high reliability

  •True galvanic isolation transformer design

  •Control designed to withstand all kinds of loads

  •Intelligent battery management to prolong battery lifecycle

  •Independent ventilation enhance durable operation under harsh environment

  •Adjustable battery numbers

  •Accept dual-mains input

  •Parallel operation with up to 4 units (option)

  •Variety of communication options available

  •Reverse phase frequency operation and supports non-neutral input

MODEL Giant 10K Giant 15K Giant 20K Giant 30K Giant 40K Giant 60K Giant 80K Giant 100K Giant 120K Giant 160K Giant 200K
CAPACITY 10KVA/8KW 15KVA/12KW 20KVA/16KW 30KVA/24KW 40KVA/32KW 60KVA/48KW 80KVA/64KW 100KVA/80KW 120KVA/96KW 160KVA/128KW 200KVA/160KW
INPUT
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph + N)
Acceptable Voltage Range 165VAC ~ 280VAC (Ph-N)
285VAC ~ 485VAC (Ph-Ph)
Frequency 50/60 Hz ± 10 %
INVERTER
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph + N)
Precision Stationary: ±1%
  Transitory: ±5% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±1 %
With mains absent ±0.1 Hz
Max. Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv) <2% (Linear Load)
<5% (Non-linear Load)
Phase Displacement 120º ±1% (balanced load)
120º ±2% (imbalances 50% of the load)
Dynamic Recovery Time 3 cycles at 90 % of the static value
Admissible Overload 110% ~ 150% 10 min ~ 60 sec
150% ~ 160% 60 sec~ 200ms
  >160% 200ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6~1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load <1%
Current Limit High overload, short-circuit: RMS Voltage Limit
  High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type Solid state
Voltage  176VAC ~ 264VAC (Ph-N)
304VAC ~ 456VAC (Ph-Ph)
Frequency 50/60 Hz ± 10 %
Activation Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 0% ~ 150% continuous working
150% ~ 180% 60 min~5 min
  >180% 5 min
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without interruption
Voltage Same as the bypass input
Frequency Same as the bypass input
Overall Efficiency Line Mode 89% 90% 91% 92%
Battery Mode 90% 91% 92% 93%
BATTERY & CHARGER
Battery Type and Numbers 12VDC x 32 pcs (29~32 pcs adjustable)
Nominal Battery Voltage 384 VDC (Based on 32pcs batteries)
Charging Method CC/CV
Precision  ±1%
Charging Current Default 10A, *Maximum=Capacity(KW)/Battery Voltage(real-time). Default 10A; Maximum 40A; 5A@ full load
Charging Voltage 432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm) 656 x 405 x 817 656 x 405 x 941 821 x 432 x 1159 975 x 554 x 1286 975 x 635 x 1326 1051x705x1646
Net Weight (Kgs) 118 120 145 193 278 365 471 573 650 735 790

 

  * The maximum current is never higher than 40A.

  Product specifications are subject to change without further notice